2025, 04, v.46 119-131
风雨作用下黄河滩区输电线杆倾覆失稳机理及影响因素分析
基金项目(Foundation): 国家自然科学基金项目(41972270); 国网河南省电力公司科技项目(521790220002); 河南省重点研发与推广专项(222102320118)
邮箱(Email):
DOI: 10.19760/j.ncwu.zk.2025064
摘要:

【目的】针对强风和暴雨天气下黄河滩区粉土地基输电线杆倾覆失稳问题,分析天气条件、杆体埋深及土体压实度对输电线杆稳定性的影响,揭示风雨作用下的倾覆破坏机理,为工程安全设计提供理论依据。【方法】通过室内模型试验与数值模拟相结合的方法,分析不同风力等级(模拟风荷载)、降雨强度(控制土体含水率)、杆体埋深及土体压实度条件下输电线杆的杆顶位移、倾斜率及周围土体位移场变化规律,探究粉土强度劣化与杆体倾覆的关联性。【结果】(1)土体含水率升高显著扩大杆后土体塑性区范围;(2)风力等级与埋深需求呈线性关系,风力每增强1级,最小安全埋深需增加0.25 m;(3)提高土体压实度可有效抑制变形,压实度每提升5%,输电线杆最小安全埋深减少0.10 m;(4)综合参数分析建立了风雨作用下输电线杆的最小安全埋深经验公式。【结论】输电线杆抗倾覆稳定性受风雨作用与土体参数协同影响,通过提升压实度及优化埋深可显著增强安全性;所提经验公式可为黄河滩区粉土地基输电线杆设计提供量化参考,兼顾经济性与可靠性。

Abstract:

【Objective】 To address the overturning instability of transmission poles in silty soil foundations in the Yellow River floodplain under extreme wind and rainstorm conditions, the impacts of weather conditions, burial depth, and soil compaction on pole stability are investigated. The failure mechanisms induced by coupled wind-rain effects are elucidated, providing theoretical foundations for safer engineering designs. 【Methods】 A combination of indoor model tests and numerical simulations was employed to analyze variations in pole-top displacement, tilt rate, and surrounding soil displacement fields of transmission poles under different wind grades(simulated wind loads), rainfall intensities(controlled soil moisture content), burial depths, and soil compaction degrees. The correlation between the silty soil strength degradation and pole overturning was systematically examined. 【Results】(1) Increased soil moisture content significantly expanded the plastic zone in the soil behind the pole.(2) A linear relationship was observed between wind grade and required burial depth, with a 0.25 m increase in minimum safe burial depth per wind force increment.(3) Enhanced soil compaction effectively suppressed deformation—for every 5% increase in compaction, the minimum safe burial depth of transmission pole decreased by 0.10 m.(4) A comprehensive parameter analysis led to the establishment of an empirical formula for determining the minimum safe burial depth under wind-rain conditions. 【Conclusion】 The anti-overturning stability of transmission poles is jointly influenced by wind-rain coupling effects and soil parameters. Enhancing compaction and optimizing the burial depth can significantly improve safety. The proposed empirical formula provides quantitative design references for transmission poles in silty soil foundations of the Yellow River floodplain, effectively balancing economy and reliability.

参考文献

[1]刘思远,夏开全.在役钢筋混凝土电杆接头承载能力试验研究[J].四川建筑科学研究,2013,39(4):99-102.[LIU S Y,XIA K Q.Experimental study on bearing capacity of inservice reinforced concrete pole joints[J].Sichuan BuildingScience,2013,39(4):99-102.]

[2]VIVEK B,SHARMA S,RAYCHOWDHURY P,et al.A study on failure mechanism of self-supported electric poles through full-scale field testing[J].Engineering Failure Analysis,2017(77):102-117.

[3]YU Q,ZHANG WANG G,et al.Analysis of tower foundation stability along the Qinghai-Tibet Power Transmission Line and impact of the route on the permafrost[J].Cold Regions Science and Technology,2016,121(1):205-213.

[4]UNCUOGLU E,LAM AN M.Numerical modelling of short pile behaviour subjected to lateral load[J].European Journal of Environmental and Civil Engineering,2012,16(2):204-235.

[5]李博,毛洪滨,姜彤,等.基于PIV技术的静压桩沉桩过程中桩周粉土位移场的试验研究[J].华北水利水电大学学报(自然科学版),2018,39(1):91-96.[LI B,MAO H B,JIANG T,et al.Experimental study on displacement field of silty soil around jacked pile during penetration based on PIV technique[J].Journal of North China University of Water Resources and Electric Power(Natural Science Edition),2018,39(1):91-96.]

[6]DENG H Z,SI R J,HU X Y,et al.Wind tunnel study on wind-induced vibration responses of a UHV transmission tower-line system[J]Advances in Structural Engineering,2013,16(7):1175-1185.

[7]FU X,LI H N.Dynamic analysis of transmission tower-line system subjected to wind and rain loads[J].Journal of Wind Engineering and Industrial Aerodynamics,2016(157):95-103.

[8]GAJAN S,MCNAMES C.Improved design of embedment depths for transmission pole foundations subject to lateral loading[J].Practice Periodical on Structural Design and Construction,2010,15(1):73-81.

[9]HANNA A,NGUYEN T Q.Shaft resistance of single vertical and batter piles driven in sand[J].Journal of Geotechnical and Geoenvironmental Engineering,2003,129(7):601-607.

[10]薛琰.复合加载模式下输电线路掏挖基础承载特性数值分析[D].吉林:东北电力大学,2018.[XUE Y.Numerical analysis of bearing characteristics of transmission line excavated foundations under combined loading modes[D].Jilin:Northeast Electric Power University,2018.]

[11]黄志全,郭芳洁,贾景超,等.郑州饱和粉土动剪切模量的试验研究[J].华北水利水电大学学报(自然科学版),2016,37(1):64-68.[HUANG Z Q,GUO F J,JIA J C,et al.Experimental study on dynamic shear modulus of saturated silt in Zhengzhou[J].Journal of North China University of Water Resources and Electric Power(Natural Science Edition),2016,37(1):64-68.]

[12]肖军华,刘建坤,彭丽云,等.黄河冲积粉土的密实度及含水率对力学性质影响[J].岩土力学,2008,29(2):409-414.[XIAO J H,LIU J K,PENG L Y,et al.Influence of compactness and water content on mechanical propertiesof Yellow River alluvial silt[J].Rock and Soil Mechanics,2008,29(2):409-414.]

[13]连峰,龚晓南,付飞营,等.黄河下游冲积粉土地震液化机理及其判别[J].浙江大学学报(工学版),2007,41(9):1492-1498.[LIAN F,GONG X N,FU F Y,et al.Seismic liquefaction mechanism and evaluation of alluvial silt in lower Yellow River region[J].Journal of Zhejiang University(Engineering Science),2007,41(9):1492-1498.]

[14]宋丹青,张洪瑞,冯兴波.饱和粉土变形特性三轴试验[J].河南科技大学学报(自然科学版),2017,38(1):52-55,6-7.[SONG D Q,ZHANG H R,FENG X B.Triaxial tests on deformation characteristics of saturated silt[J].Journal of Henan University of Science and Technology(Natural Science Edition),2017,38(1):52-55,6-7.]

[15]中华人民共和国水利部.土工试验方法标准:GB/T50123—2019[S].北京:中国计划出版社,2019.[Ministry of Water Resources of the People's Republic of China.Standard for geotechnical testing method:GB/T 50123—2019[S].Beijing:China Planning Press,2019.]

[16]YUAN B X,LI Z H,ZHAO Z Q,et al.Experimental study of displacement field of layered soils surrounding laterally loaded pile based on transparent soil[J].Journal of Soils and Sediments,2021,21(9):3072-3083.

[17]国家能源局.架空输电线路基础设计技术规程:DL/T5219—2014[S].北京:中国计划出版社,2014.[National Energy Administration.Technical code for design of overhead transmission line foundations:DL/T 5219—2014[S].Beijing:China Planning Press,2014.]

[18]中华人民共和国住房和城乡建设部.城镇道路工程施工与质量验收规范:GJJ1—2008[S].北京:中国建筑工业出版社,2008.[Ministry of Housing and Urban-Rural Development of the People's Republic of China.Code for construction and quality acceptance of urban road engineering:CJJ1—2008[S].Beijing:China Architecture&Building Press,2008.]

[19]张熙坤.压实黄土状土静动力特性试验研究[D].石家庄:石家庄铁道大学,2023.[ZHANG X K.Experimental study on static and dynamic characteristics of compacted loess-like soil[D].Shijiazhuang:Shijiazhuang Tiedao University,2023.]

[20]肖成志,李晓峰,张静娟.压实度和含水率对含砂粉土性质的影响[J].深圳大学学报(理工版),2017,34(5):501-508.[XIAO C Z,LI X F,ZHANG J J.Effects of compaction degree and moisture content on properties of sandy silt[J].Journal of Shenzhen University(Science and Engineering),2017,34(5):501-508.]

[21]中华人民共和国住房和城乡建设部.66kV及以下架空电力线路设计规范:GB 50061—2010[S].北京:中国计划出版社,2010.[Ministry of Housing and Urban-Rural Development of the People's Republic of China.Code for design of 66 kV and under overhead electrical lines:GB50061—2010[S].Beijing:China Planning Press,2010.]

[22]杨尧,胡宽.输配电线路运行与检修(第二版)[M].北京:中国电力出版社,2019.[YANG Y,HU K.Operation and maintenance of transmission and distribution lines(2nd ed.)[M].Beijing:China Electric Power Press,2019.]

[23]中华人民共和国住房和城乡建设部.110kV~750kV架空输电线路设计规范:GB 50545—2010)[S].北京:中国计划出版社,2010.[Ministry of Housing and Urban-Rural Development of the People's Republic of China.Code for design of 110 kV~750 kV overhead transmission lines:GB50545—2010[S].Beijing:China Planning Press,2010.]

[24]王纪军,竹磊磊,胡彩虹,等.陇海—京广线沿线河南段年最大风速和年最大积雪深度重现期研究[J].气象与环境科学,2016,39(3):9-14.[WANG J J,ZHU L L,HU C H,et al.Study on return period of annual maximum wind speed and snow depth along Henan section of Longhai-Jingguang Railway[J].Meteorological and Environmental Sciences,2016,39(3):9-14.]

[25]BROMS,BENGT B.Lateral resistance of piles in cohesive soils[J].Journal of the Soil Mechanics and Foundations Division,1964,90(2):27-63.

基本信息:

DOI:10.19760/j.ncwu.zk.2025064

中图分类号:TM75;TU311.2

引用信息:

[1]闫长斌,程沛铭,南钰,等.风雨作用下黄河滩区输电线杆倾覆失稳机理及影响因素分析[J].华北水利水电大学学报(自然科学版),2025,46(04):119-131.DOI:10.19760/j.ncwu.zk.2025064.

基金信息:

国家自然科学基金项目(41972270); 国网河南省电力公司科技项目(521790220002); 河南省重点研发与推广专项(222102320118)

发布时间:

2024-06-26

出版时间:

2024-06-26

网络发布时间:

2024-06-26

检 索 高级检索